Detection: Carbon Monoxide (CO);
Frequency band: 868.0 … 868.6 MHz;
Radio communication distance (in open area): 2000 m – ABAX2 @ ACU-220, 1200 m – ABAX2 @ ACU-280;
Battery power: 1 x battery CR123A 3 V (included);
Support : | Wireless signaling systems SATEL ABAX2 |
Detection : | Carbon monoxide (CO) |
Alarm : | audible (buzzer) Optical (LED) |
Alarm concentration : | 50 … 75 ppm 75 minutes 75 … 120 ppm for 25 minutes > 120 ppm in 1 minute |
Frequency band : | 868.0 … 868.6 MHz |
Radio distance (in open area) : | 2000 m – ABAX2 @ ACU-220, 1200 m – ABAX2 @ ACU-280 |
Usage : | Indoor |
Battery powered : | 1 x battery CR123A 3 V (included) |
Current consumption : | 120 mA (max) 14 µA (Standby mode) – Automatic operation 62 µA (Standby mode) – ABAX2 |
Battery duration : | ~ 5 years – Automatic work ~ 2 years – ABAX2 |
Digital temperature compensation : | + |
Recommended mounting height : | 1.5 … 2.0 m above ground |
Main features : | Electrochemical carbon monoxide sensor Detector lifetime: 10 years Test mode Gas sensor maintenance Fault signaling battery status control Low battery signal Option “ECO” provides up to four times the battery life (ABAX2 only) Two-way encrypted radio communication – AES Protection against interference thanks to frequency shift ensures reliable transmission Installed temperature sensor, Temperature measurement: 0 °C … 55 °C Anti-sabotage protection measures – opening case |
Working temperature : | 0 °C … 55 °C |
Weight : | 0.14 kg (without battery) |
Dimensions : | 108x 49 mm |
Manufacturer / Brand : | SATEL |
ACMD-200 wireless carbon monoxide sensor that detects the dangerous concentration of this gas in the monitored room.
The digital temperature compensation mechanism allows working in a wide temperature range.
The ACMD-200 can operate automatically or as a two-way ABAX2 wireless system
Exceeding the threshold gas concentration is signaled by optical and acoustic signals
It is recommended to install the device at least 1.5 … 2.0 m above the floor